ERROR COAST RD Precision Station : Data Error (all PM)
18 February 2025 - 19 February 2025
18/02/2025 10:00 PM stopped reporting. Other channels are ok.
19/02/2025 14:00 Acoem downloaded the configuration again, but no difference.
19/02/2025 16:45 On-site investigation - Fidas protocol setting has somehow been set to Ascii - it should be Bayer Hessen at 56700 baud.
Manually re-set this and rebooted. PM restarted.
Data for PM will be missing during this period.